首页> 外文会议>International Conference on Reliability of Electrical Products and Electrical Contacts(ICREPEC 2004); 20040828-31; Suzhou(CN) >ORIGIN, DETECTION AND COST OF CONNECTOR DEGRADATION IN ELECTRICAL TRANSMISSION AND DISTRIBUTION SYSTEMS
【24h】

ORIGIN, DETECTION AND COST OF CONNECTOR DEGRADATION IN ELECTRICAL TRANSMISSION AND DISTRIBUTION SYSTEMS

机译:输配电系统中连接器退化的起源,检测和成本

获取原文
获取原文并翻译 | 示例

摘要

The paper summarizes the major mechanisms responsibie for the degradation of electrical connectors in transmission and distribution systems. A simple model of an electrical contact is described, that reproduces the degradation pattern of connector. From this model, the paper illustrates the importance of detecting the early stages of connector degradation to prevent catastrophic failure of electrical connections. The paper reviews results of recent "live-line" resistance measurements on high-power connectors and summarizes current observations of the impact of connector design on connector service performance in distribution networks. The limitations of infrared thermography for detecting connector degradation are summarized. Finally, the paper addresses the consequence of connector degradation on the operating cost of a power line.
机译:本文总结了传输和分配系统中电连接器性能下降的主要机制。描述了一种简单的电触点模型,该模型可再现连接器的退化模式。通过该模型,本文说明了检测连接器退化的早期阶段以防止电气连接灾难性故障的重要性。本文回顾了最近在大功率连接器上进行的“实线”电阻测量结果,并总结了当前对连接器设计对配电网络中连接器服务性能影响的观察结果。总结了红外热成像技术在检测连接器退化方面的局限性。最后,本文讨论了连接器性能下降对电源线运行成本的影响。