首页> 外文会议>International Conference on Electrical Machines and Systems(ICEMS 2005) vol.1; 20050927-29; Nanjing(CN) >Study on New Leading-out Mode of Neutral Points of Large-sized Turbo-generator
【24h】

Study on New Leading-out Mode of Neutral Points of Large-sized Turbo-generator

机译:大型汽轮发电机中性点新型引出方式研究

获取原文
获取原文并翻译 | 示例

摘要

To supply overall protection for large-sized turbo-generator, a new approach about leading-out mode of neutral points and disposition of protection schemes is firstly presented in this paper. To check up the sensitivity of the new protection scheme, two turbo-generators with 300MW are simulated using the Multi-loop method. Simulation results indicate the performance of the new protection scheme is much better than that of the traditional protection. Without adding hardware investment, the new leading-out mode is agreed by electrical machine designers.
机译:为了给大型汽轮发电机提供全面的保护,本文首次提出了一种关于中性点引出方式和保护方案布置的新方法。为了检验新保护方案的敏感性,使用多回路方法模拟了两台300MW的涡轮发电机。仿真结果表明,新的保护方案的性能远远优于传统的保护方案。在不增加硬件投资的情况下,电机设计人员同意采用新的导出模式。