The grounding resistance of the transmission line tower is an important parameter to ensure the safe and stable operation of the power system. The accurate grasp of this parameter is the premise of formulating appropriate lightning protection measures for the power system. Since the periodic test task of the tower grounding resistance is heavy and half of the towers are located in the mountainous area, the conventional three-pole test method is difficult to carry out, so most of the tests are currently carried out by the clamp method. Generally, the high-voltage transmission line tower in operation senses the interference signal with amplitude variation on the grounding device. However, the caliper test instrument in the domestic market is weak in anti-interference, which results in large test error and cannot meet the requirements of on-site measurement. This paper presents an improved caliper type tower grounding resistance measurement method. The method is based on the principle of the clamp method, injects the adjustable frequency excitation voltage source, automatically switches the excitation source frequency through the self-check interference signal frequency band, avoids the interference signal frequency band, and obtains the response signal by loading the digital filtering module, and calculates the in-service Tower grounding resistance. The method has passed the test verification, which greatly saves human and financial resources, improves the accuracy value of the grounding resistance of the transport tower, and has a large application prospect.
机译:输电线路铁塔的接地电阻是确保电力系统安全稳定运行的重要参数。准确掌握该参数是为电力系统制定适当的防雷措施的前提。由于塔架接地电阻的定期测试任务繁重,并且一半的塔架位于山区,因此传统的三极测试方法难以执行,因此目前大多数测试是通过钳位方法进行的。通常,运行中的高压输电线路铁塔在接地设备上感测幅度变化的干扰信号。但是,国内市场的卡尺测试仪抗干扰能力较弱,导致测试误差较大,无法满足现场测量的要求。本文提出了一种改进的卡尺式铁塔接地电阻测量方法。该方法基于钳位法原理,注入可调频率的激励电压源,通过自检干扰信号频段自动切换激励源频率,避开干扰信号频段,并通过加载获得响应信号。数字滤波模块,并计算在用塔架接地电阻。该方法通过了测试验证,大大节省了人力和财力,提高了运输塔接地电阻的精度值,具有广阔的应用前景。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号