Differentiation research on closing overvoltage of headline-cable comprehensive transmission type with double circuit transmission lines on same tower

机译:同一塔架上双回路输电线路的标题电缆综合输电方式闭合过电压的区别研究

获取原文

摘要

To research the close overvoltage transient characteristic of headline-cable comprehensive transmission type with double circuit transmission lines on same tower, a 220kV power system was selected to build the transient model of headline-cable comprehensive transmission type with double circuit transmission lines on same tower by EMTP, the characteristics of the close overvoltage and the reclose overvoltage after single phase grounding fault were researched totally. Ultimately, the main factors effect on close overvoltage were analyzed. The results demonstrated that the amplitudes of overvoltage were mainly related to close phase angles with its range from 1.17p.u to 2.14p.u. It's best to close at the phase angle from 210°-240° considering the characteristic of arrester. The amplitude of reclose overvoltage was lower than that of close overvoltage. It's appropriate to close the circuit breaker on source side after closing the circuit breaker on the load side to avoid damaging the potential transformer joint with the bus of load. The amplitude of close overvoltage when the transmission line was whole headline was lower than that when the transmission line was headline and cable. It's really possible to occur resonance overvoltage if the transmission line was the whole cable. The amplitude of the over-voltage can be reduced only if the suitable operation types and running types.
机译:为研究双塔输电线路在同一塔架上的大头电缆综合输电方式的过电压瞬态特性,选择了220kV电力系统,通过双塔输电线路在塔上进行双头输电线路的瞬态模型建立。全面研究了EMTP,单相接地故障后的闭合过电压和重闭合过电压的特性。最终,分析了影响闭合过电压的主要因素。结果表明,过电压的幅度主要与闭合相位角有关,其范围为1.17p.u至2.14p.u。考虑到避雷器的特性,最好以210°-240°的相角关闭。重合闸过电压的幅度小于合闸过电压的幅度。在合上负载侧的断路器之后,应在电源侧合上断路器,以免损坏电位计与负载母线的连接。传输线为整体标题时的闭合过电压幅度低于传输线为整体标题和电缆时的闭合过电压幅度。如果传输线是整个电缆,则确实有可能发生谐振过电压。仅当合适的运行类型和运行类型时,才能降低过电压的幅度。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号