Industry standards for shielded medium voltage power cables, 5nthrough 46 kV, have recently been revised, changing the direct currentntest voltages for field tests and test durations, and limiting tests tonnewly installed cables. The following industry groups' specificationsnand standards provide different guidelines for DC field tests forncross-linked polyethylene and ethylene propylene rubber insulatedncables: Institute of Electrical and Electronic Engineers (IEEE);nInsulated Cable Engineers Association (ICEA); and the Association ofnEdison Illuminating Companies (AEIC). These specifications and standardsnare discussed showing the differences in the recommendations and why thendifferences exist. The conclusion provides a guide for the DC fieldntesting of shielded medium voltage power cables based on these industrynstandards
机译:最近修订了5n至46 kV屏蔽中压电力电缆的行业标准,更改了针对现场测试和测试持续时间的直流ntest电压,并限制了新安装的电缆的测试。以下行业组织的规范和标准为交联聚乙烯和乙丙橡胶绝缘电缆的直流现场测试提供了不同的准则:电气和电子工程师协会(IEEE);绝缘电缆工程师协会(ICEA);和爱迪生照明公司协会(AEIC)。讨论了这些规范和标准,以显示建议中的差异以及存在差异的原因。结论为基于这些行业标准的屏蔽中压电力电缆的直流现场测试提供了指南。