Transformers operating in power networks are subjected to lightning, network switching phenomena like protection action and selected failure stages. Those effects may result in additional stresses on insulation system of the windings in form of external overvoltages or internal resonances in windings caused by fast dU/dt transients. This paper presents the method for reduction of dU/dt based on specially designed upstream choke device. The new concept employs the upstream impedance placed on high voltage line and application dependent surge capacitance. The upstream choke mitigation impact will be presented for induced lightning stroke producing the fast surge with high dU/dt on the transformer terminals. The comparison of insulation stress for various transients with different rise time properties will be shown. The simulation results along with real measurements of choke operation will be compared.
机译:在电力网络中运行的变压器会遭受雷击,网络切换现象,例如保护动作和选定的故障阶段。这些影响可能导致由外部dU / dt瞬变引起的外部过电压或绕组内部共振,从而对绕组的绝缘系统产生额外的应力。本文提出了一种基于特殊设计的上游节流装置的降低dU / dt的方法。新概念采用了放置在高压线上的上游阻抗和取决于应用的浪涌电容。上游扼流圈的缓解影响将针对感应雷击产生,在变压器端子上产生高dU / dt的快速浪涌。将显示具有不同上升时间特性的各种瞬态的绝缘应力的比较。仿真结果与扼流圈操作的实际测量结果将进行比较。