首页> 外文期刊>IEEE Transactions on Power Delivery >Reduction in distribution transformer failure rates and nuisance outages using improved lightning protection concepts
【24h】

Reduction in distribution transformer failure rates and nuisance outages using improved lightning protection concepts

机译:使用改进的防雷概念,减少配电变压器的故障率和扰民故障

获取原文
获取原文并翻译 | 示例
       

摘要

This paper presents a case study of an overhead distribution feeder in a very high keraunic area. The feeder was experiencing approximately twice the number of lightning caused transformer failures per year than any other distribution feeder in the area. In an attempt to lower the outage rate and the repair costs, the lightning protection for this feeder was studied and a new protection system was installed. The first section of this paper discusses the outage history of this feeder and existing transformer overvoltage protection. It then details the steps that were taken to improve the protection so acceptable customer service could be achieved. The interruption data results for one year after the protection changes were implemented are then presented. The results from the field trial of the new lightning protection scheme exhibit a significant improvement in the feeder service reliability. The last section of this paper is a compilation of teardown data of failed distribution transformers. The analysis includes failed transformers from the study feeder, and failed transformers from the same electric utility, but not part of the feeder study. The causes of the transformer failures were tabulated. The results from the teardowns indicate that a high percentage of distribution transformers with interlaced and noninterlaced secondary windings fail from low-side voltage surges.
机译:本文介绍了一个非常高的煤油地区的架空分配给料机的案例研究。与该地区的其他任何配电馈线相比,该馈线每年经历的雷击变压器故障次数大约是其两倍。为了降低停电率和维修成本,对该馈线进行了防雷保护,并安装了新的保护系统。本文的第一部分讨论了该馈线的断电历史和现有的变压器过压保护。然后详细介绍了为提高保护水平而采取的步骤,以便可以实现可接受的客户服务。然后介绍实施保护更改后一年的中断数据结果。新的防雷方案的现场试验结果显示,支线服务可靠性大大提高。本文的最后一部分是故障配电变压器的拆解数据的汇编。分析包括来自研究馈线的故障变压器,以及来自同一电力公司但不属于馈线研究的一部分的故障变压器。列出了变压器故障的原因。拆卸的结果表明,具有交错和非交错次级绕组的配电变压器中,有很大一部分会因低端电压浪涌而失效。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号