首页> 外文会议>International symposium on high voltage engineering;ISH2003 >Improvements on a new method to correct the humidity effect onLightning Impulse Testing
【24h】

Improvements on a new method to correct the humidity effect onLightning Impulse Testing

机译:改进了纠正雷电冲击测试中湿度影响的新方法的方法

获取原文
获取外文期刊封面目录资料

摘要

The Humidity Correction Factor forLightning Impulse Tests is carried out according to astandard international procedure. However, thisprocedure is not suitable to application in shortdistance air gaps typical of medium voltage apparatus.This paper deals with the present improvement of anew proposal to define a humidity correction factorsuitable to application in medium voltage apparatus.The developed procedure was based in testing resultson Sphere – sphere and Rod – Rod gaps. All data wasobtained at the High Voltage Laboratory of FederalUniversity of Itajubá using a 450kV – 1.25kJ impulsevoltage generator.
机译:湿度校正因子 雷电冲击测试根据 标准的国际程序。但是这个 该程序不适合短时间的应用 中压设备典型的距离气隙。 本文讨论了当前的改进 定义湿度校正因子的新建议 适用于中压设备。 制定的程序基于测试结果 在球体–球体和杆–杆间隙上。所有数据原为 在联邦高压实验室获得 Itajubá大学使用450kV – 1.25kJ脉冲 电压发生器。