首页> 外文会议>Electrical insulation conference >Testing of HVDC arresters according to new IEC standard with emphasis on effect from operating voltage
【24h】

Testing of HVDC arresters according to new IEC standard with emphasis on effect from operating voltage

机译:根据新的IEC标准测试HVDC避雷器,重点是工作电压的影响

获取原文

摘要

Surge arresters in HVDC converter stations are subjected to continuous operating voltages with very different waveforms compared to arresters for normal a.c. applications. Since the protection levels achievable are directly proportional to how high the arresters can be stressed continuously, accurate knowledge of long-term stability and continuous power losses for the applied voltage waveforms are decisive. In the past it has been difficult to produce and perform tests on metal-oxide (MO) resistors with these waveforms, but today they can be readily produced by a high-voltage power amplifier system. More accurate knowledge of the performance of the MO resistors thus forms the basis for obtaining accurate designs of the arresters.
机译:与普通交流电避雷器相比,高压直流换流站中的电涌避雷器要承受的连续工作电压具有非常不同的波形。应用程序。由于可达到的保护等级与避雷器可以承受的压力直接成正比,因此对于所施加电压波形的长期稳定性和连续功率损耗的准确了解至关重要。过去,很难用这些波形在金属氧化物(MO)电阻上进行生产和测试,但如今,它们可以通过高压功率放大器系统轻松生产。因此,对MO电阻器性能的更准确的了解构成了获得避雷器精确设计的基础。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号