首页> 外文会议>Advanced Power System Automation and Protection (APAP), 2011 International Conference on >Implementation of non-communication protection of double circuit line systems based on integrated protection platform
【24h】

Implementation of non-communication protection of double circuit line systems based on integrated protection platform

机译:基于集成保护平台的双回线系统非通信保护的实现

获取原文
获取原文并翻译 | 示例

摘要

The implementation of non-communication protection of double circuit line systems based on two independent relays has disadvantages like information shareless,complex connection and lack of economic. This paper researched the implementation of non-communication protection of double circuit line systems based on one relay - the integrated protection platform. Hardware structure of the integrated protection platform is described, and software flow of non-communication protection of double circuit line systems which implemented on the integrated protection platform is also described. Large number of RTDS experiments proved that, according to various asymmetrical fault and symmetrical fault, this protection scheme has reliable and sensitive action performance. It is proved that the implement non-communication protection of double circuit line systems based on the intergrated protection platform is feasible.
机译:基于两个独立的继电器实现双回线系统的非通信保护,存在信息无共享,连接复杂,缺乏经济性等缺点。本文研究了基于一个继电器-综合保护平台的双回线系统的非通信保护的实现。描述了综合保护平台的硬件结构,还描述了在综合保护平台上实现的双回线系统非通信保护的软件流程。大量的RTDS实验证明,针对各种不对称故障和对称故障,该保护方案具有可靠,灵敏的动作性能。实践证明,基于集成保护平台实现双回线系统的非通信保护是可行的。