首页> 外文会议>9th International Conference on Indoor Air Quality and Climate Vol.1, Jun 30-Jul 5, 2002, Monterey, California >DOUBLE SKIN FACADE AND HYBRID VENTILATION OF THE ING HOUSE AMSTERDAM (ING BANK HQ)
【24h】

DOUBLE SKIN FACADE AND HYBRID VENTILATION OF THE ING HOUSE AMSTERDAM (ING BANK HQ)

机译:ING房屋阿姆斯特丹(ING BANK HQ)的双皮肤外观和混合通风

获取原文
获取原文并翻译 | 示例

摘要

The ING-HQ is characterised by a full transparent 2~(nd) skin facade. This transparency in combination with high indoor temperature requirements and the wish for low energy consumption was an interesting design challenge. The cavity between inner and outer facades can be ventilated in a controlled way using glass vents to: either discard excess heat or for hybrid ventilation. Interaction between active fapade and climate system results in an intelligent building. The big amount of glass was only acceptable in case of very low solar energy transmittance (g-value). TNO Building and Construction Research (Delft, The Netherlands) did research to check our prognosis. The "Advanced Window Information System", was used in combination with the CFD code WISH-3D. Validation of the CFD-model for this specific situation was done by laboratory measurements in a full-scale model. The g-value measured in the laboratory proved to be 0,07. After corrections a practical value of 0,08-0,11 was derived.
机译:ING-HQ的特征是全透明的2〜(nd)皮肤外墙。这种透明性与高室内温度要求以及对低能耗的渴望相结合是一个有趣的设计挑战。内外墙之间的空腔可以使用玻璃通风口以受控方式通风,以:散发多余的热量或进行混合通风。主动式幕墙与气候系统之间的相互作用产生了一座智能建筑。仅在非常低的太阳能透射率(g值)的情况下才可接受大量的玻璃。 TNO建筑工程研究公司(荷兰代尔夫特)进行了研究以检查我们的预后。 “高级窗口信息系统”与CFD代码WISH-3D结合使用。针对这种特殊情况的CFD模型验证是通过实验室测量的全面模型进行的。在实验室中测得的g值为0.07。校正后得出的实际值为0,08-0,11。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号