The boiler-model based unit control in once-through boilers

机译:直流锅炉中基于锅炉模型的单元控制

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

With different time behavior of the boiler and the turbine causes an energy imbalance between two main control variable megawatts (MW) and throttle pressure to fluctuate, the throttle pressure lag and excessive overshoot in coordinated unit control cannot be avoided. There are two methods to improve process dynamic response. When the fuel is step up (step down) process delays of 3~5minutes occur before steam flow and pressure increase. By analyzing results, a model pressure set point and turbine set point can be developed that corresponds to the order of boiler response. A second method is to use a transport turbine master feedforward model to reduce pressure deviations at initial stage of load change. As a consequence, the coordinated unit control response is stable and the result is very good.
机译:由于锅炉和涡轮机的时间行为不同,导致两个主控制变量兆瓦(MW)之间的能量不平衡,并且节气门压力波动,因此无法避免节气门压力滞后和协调单元控制中的过冲。有两种方法可以改善过程动态响应。当燃油升压(降压)时,在蒸汽流量和压力增加之前,将发生3到5分钟的过程延迟。通过分析结果,可以建立与锅炉响应顺序相对应的模型压力设定点和涡轮设定点。第二种方法是使用运输涡轮机主前馈模型来减少负载变化初始阶段的压力偏差。结果,协调的单元控制响应是稳定的并且结果非常好。