Calculation, simulation and measurement for short-circuit reactance of distribution transformers with long-circular double windings

机译:长圆形双绕组配电变压器短路电抗的计算,仿真和测量

获取原文
获取原文并翻译 | 示例

摘要

In this paper, the structure characteristics of long circular coil of the double winding distribution transformer are introduced firstly, and the calculation method is presented in the case of the transformer of SCB10-1250/10/0.4. Secondly, the transformer is modeled through 3D magnetostatic field analysis in Ansoft-Maxwell, where simulation calculation of the short-circuit reactance is based on the energy method. Finally, the short-circuit reactance is tested that carried out to prove the correctness of the presented calculation method. The numerical error of the short-circuit reactance is less than 3% through an analytical comparison among the three results. Measurement results show that the short-circuit reactance of long-circular windings of distribution transformers have been calculated accurately by simulation calculation and it can meet the requirements of the engineering applications.
机译:本文首先介绍了双绕组配电变压器的长圆形线圈的结构特点,并针对SCB10-1250 / 10 / 0.4变压器的情况提出了计算方法。其次,在Ansoft-Maxwell中通过3D静磁场分析对变压器建模,其中短路电抗的仿真计算基于能量方法。最后,对短路电抗进行了测试,以证明所提出的计算方法的正确性。通过对三个结果的分析比较,短路电抗的数值误差小于3%。测量结果表明,通过仿真计算可以准确计算出配电变压器长圆绕组的短路电抗,可以满足工程应用的要求。