首页> 外文会议>CIRED 2012;Workshop on Integration of Renewables into the Distribution Grid >Incorporating harmonic limits into assessment of the hosting capacity of active networks
【24h】

Incorporating harmonic limits into assessment of the hosting capacity of active networks

机译:将谐波限制纳入活动网络的承载能力评估中

获取原文
获取原文并翻译 | 示例

摘要

Harmonic emissions from converter-interfaced distributed generation connection can potentially lead to voltage distortion levels that are above applicable standards. The risk increases as greater connection volumes are facilitated by Active Network Management schemes. By incorporating harmonic limits into assessment of the hosting capacity of active networks, this paper demonstrates that by incorporating harmonic levels at the planning stage can prevent inadvertent restrictions on the integration of renewables. Other aspects considered include: the impact of active network controls on harmonic propagation and hosting capacity and the role of active harmonic mitigation methods.
机译:转换器接口的分布式发电连接产生的谐波辐射有可能导致电压畸变水平超出适用标准。主动网络管理方案有助于增加连接量,从而增加风险。通过将谐波极限纳入有源网络承载能力的评估中,本文表明,通过在规划阶段纳入谐波水平可以防止对可再生能源整合的无意限制。考虑的其他方面包括:有源网络控制对谐波传播和承载能力的影响以及有源谐波缓解方法的作用。