首页> 外文会议>2012 Workshop on Integration of Renewables into the Distribution Grid >LOAD LOSS EVALUATION FOR DISTRIBUTION TRANSFORMERS IN NETWORKS WITH LARGE AMOUNTS OF PHOTOVOLTAIC GENERATION-A CASE STUDY USING AMR DATA
【24h】

LOAD LOSS EVALUATION FOR DISTRIBUTION TRANSFORMERS IN NETWORKS WITH LARGE AMOUNTS OF PHOTOVOLTAIC GENERATION-A CASE STUDY USING AMR DATA

机译:大量光伏发电网络中配电变压器的负载损失评估-以AMR数据为例的案例研究

获取原文
获取原文并翻译 | 示例

摘要

The impact of photovoltaic (PV) generation to the evaluation of load losses have been analysed in this paper using data from AMR meters.PV generation has been simulated using sun radiation data together with AMR data for 14 low voltage networks.These networks have different characteristics when it comes to number of customers,types of customers and type of heating.The results show that PV generation in networks with district heating and industries gives the biggest reductions in loss utilisation time,up to 20%.Smaller reductions have been obtained in other networks mainly in the range 4-12%.These differences are however in the same range as the difference between using classical approach to determine the loss utilisation time and AMR approach.The low impact to loss utilisation time doesn't motivate a specific loss evaluation for networks with large amount of PV generation.
机译:本文利用AMR仪表的数据分析了光伏发电对评估负载损失的影响,并利用太阳辐射数据和AMR数据对14个低压网络模拟了光伏发电,这些网络具有不同的特性从客户数量,客户类型和供热类型来看。结果表明,在具有区域供热和工业网络的光伏发电中,损失利用时间最多减少,最多可减少20%。网络主要在4-12%的范围内。但是,这些差异与使用经典方法确定损失利用时间和AMR方法之间的差别在同一范围内。对损失利用时间的低影响不会促使进行特定的损失评估适用于拥有大量光伏发电的网络。