摘要

This paper describes the development of an out of step relay using model based design (MBD) approach. Results of simulation testing on the model and target are also discussed. The predictive out of step algorithm is used to detect severe power swings and out of step conditions between different sections of a power system. To satisfy the functional specifications, the instability detection must be done in a rapid, reliable and safe way. The development of this device has been carried out in collaboration with Hydro-Quebec. The predictive out of step detection is realized by using fuzzy logic, which processes variables derived from the voltage and current on the transmission line. System level modeling and simulation has been done in Matlab / Simulink. Automated code generation has been used to produce the target software. Target implementation has been successful on the hardware platform.
机译:本文介绍了使用基于模型的设计(MBD)方法开发失步继电器的方法。还讨论了对模型和目标进行仿真测试的结果。预测性失步算法用于检测电力系统不同部分之间的严重功率摆幅和失步状况。为了满足功能规格,必须以快速,可靠和安全的方式进行不稳定性检测。该设备的开发已与Hydro-Quebec合作进行。预测性失步检测是通过使用模糊逻辑实现的,该逻辑处理从传输线上的电压和电流得出的变量。在Matlab / Simulink中已经完成了系统级的建模和仿真。自动代码生成已用于生成目标软件。目标实现已在硬件平台上成功完成。