首页> 外文会议>2002 IEEE Region 10 Conference on Computers, Communications, Control and Power Engineering (IEEE TENCOM'02) Vol.3; Oct 28-31, 2002; Beijing, China >GROUND-FAULT PROTECTION BASED ON ACTIVE COMPONENT OF ZERO-SEQUENCE CURRENT IN RESISTANCE NEUTRAL GROUNDED DISTRIBUTION SYSTEMS
【24h】

GROUND-FAULT PROTECTION BASED ON ACTIVE COMPONENT OF ZERO-SEQUENCE CURRENT IN RESISTANCE NEUTRAL GROUNDED DISTRIBUTION SYSTEMS

机译:基于零序电流有功分量的电阻中性点接地配电系统接地故障保护

获取原文
获取原文并翻译 | 示例

摘要

A new principle of ground-fault protection for resistance neutral grounded systems is presented. Unlike previous work, the principle realizes selective ground-fault protection by getting the active current component that is resulted from the neutral resistor and only exists in the faulted line. The getting of the active current is presented in detail. On the basis of this principle, a selective ground-fault protection system and device have been developed.
机译:提出了中性点接地系统接地故障保护的新原理。与以前的工作不同,该原理通过获取由中性电阻产生的,仅存在于故障线路中的有功电流分量来实现选择性接地故障保护。详细介绍了有功电流的获取。基于这一原理,开发了一种选择性的接地故障保护系统和装置。