首页> 外文会议>SMiRT 16;International conference on structural mechanics in reactor technology >Seismic Reliability Evaluation of Electrical Power Transmission Systems and itsEffect on Core Damage Frequency
【24h】

Seismic Reliability Evaluation of Electrical Power Transmission Systems and itsEffect on Core Damage Frequency

机译:电力传输系统的地震可靠性评估及其对铁心损伤频率的影响

获取原文
获取原文并翻译 | 示例

摘要

This paper presents the results of seismic capacity evaluation of electrical transmission equipment in substations usingrnthe damage records in the case of the Southern Hyogo Prefecture earthquake in 1995, the seismic reliability of electricalrnpower transmission systems and its influence on core damage frequency of a nuclear power plant. Since damages ofrnelectrical equipment in substations were found mostly in those manufactured before a revision of seismic design guidelinernin 1980, seismic capacity of electrical equipment was separately evaluated for those manufactured before and after thernrevision. The failure probability of electrical power transmission systems was higher than the occurrence probability of lossrnof offsite power due to failures of ceramic insulators in the site switchyard and its effect on the core damage frequency ofrnthe nuclear power plant was not significant.
机译:利用1995年兵库县南部地震的破坏记录,电力传输系统的抗震可靠性及其对核电厂核心破坏频率的影响,介绍了变电站输电设备抗震能力的评估结果。由于变电站中电气设备的损坏大多发生在1980年修订抗震设计准则之前制造的设备中,因此,针对修订前后的电气设备的抗震能力分别进行了评估。电力传输系统的故障概率高于现场开关站中的陶瓷绝缘子故障导致的场外损耗的发生概率,并且对核电站核心损坏频率的影响不显着。