Steady-State Analysis of a Faulted Three-Phase Four-Wire System Supplying Induction Motors with Neutrals Connected and Other Single-Phase Line-to-Neutral Loads

机译:一个故障三相四线制系统的稳态分析,提供中性点连接的感应电动机和其他单相线路到中性负载

获取原文

摘要

Four wire Wye connected ac power systems exhibit peculiar steady state fault characteristics when the fourth wire of three phase induction motors is connected. The loss of one phase of power source due to a series or shunt fault results in currents higher than anticipated on the remaining two phases. A theoretical approach to compute the fault currents and voltages is developed. A FORTRAN program is included in the appendix.