The automatic sprinkler system experiences of the United States Department of Energy and its predecessor agencies are analyzed. Based on accident and incident files in the Office of Operational Safety and on supplementary responses, 587 incidents including over 100 fires are analyzed. Tables and figures, with supplementary narratives discuss fire experience by various categories such as number of heads operating, type of system, dollar losses, failures, extinguished vs. controlled, and types of sprinkler heads. Use is made of extreme value projections and frequency-severity plots to compare past experience and predict future experience. Non-fire incidents are analyzed in a similar manner by cause, system types and failure types. Discussion of no-loss incidents and non-fire protection water systems is included. The author's conclusions and recommendations and appendices listing survey methodology, major incidents, and a bibliography are included. (ERA citation 07:053153)