Tube-to-tube heat transfer degradation effect on finned-tube heat exchangers

机译:管对管传热退化对翅片管换热器的影响

获取原文
获取原文并翻译 | 示例
           

摘要

Tube-to-tube heat transfer is suspected to affect the overall capacity of most finned-tube heat exchangers running subcooled (single-phase) simple substances, or zeotropic mixtures, as coolants. A simplified numerical model is presented and used for simulating the heat transfer process of air flowing in between two parallel fins of a finned-tube heat exchanger with known tube temperatures. The objective of the numerical simulation is to detect the existence of tube-to-tube heat transfer and the corresponding detrimental impact it might have on the overall capacity of the heat exchanger. The numerical simulation considers a 4 x 3 finned-tube, single-phase, air-water heat exchanger with data provided by the National Institute of Standards and Technology (NIST). Results indicate the existence of strong tube-to-tube heat transfer along the fins (particularly among neighboring tubes presenting very different temperatures, as expected). The tube-to-tube heat transfer phenomenon is shown to account for approximately 20% of the heat exchanger capacity. Thin adiabatic layers placed along the fin surface are shown, also through numerical simulations, to be very effective in interrupting the tube-to-tube heat transfer phenomenon. A simplified analytical procedure to estimate the tube-to-tube heat transfer effect of any finned-tube heat exchanger, suggested as a design tool, is satisfactorily tested against the numerical results. [References: 13]
机译:怀疑管间传热会影响大多数以过冷(单相)单质或共沸混合物作为冷却剂运行的翅片管热交换器的整体容量。提出了一种简化的数值模型,用于模拟在已知管温度下在翅片管热交换器的两个平行翅片之间流动的空气的传热过程。数值模拟的目的是检测管到管传热的存在及其对热交换器总容量的不利影响。数值模拟考虑了一个4 x 3翅片管,单相空气-水热交换器,其数据由美国国家标准技术研究院(NIST)提供。结果表明,沿着翅片存在强烈的管对管传热(特别是与预期的温度差异很大的相邻管之间)。管与管之间的热传递现象显示出约占热交换器容量的20%。还通过数值模拟显示了沿翅片表面放置的绝热薄层,对于中断管对管的传热现象非常有效。作为数值计算工具,一种简化的分析程序可用来评估任何翅片管式换热器的管对管传热效果,并与数值结果进行了令人满意的测试。 [参考:13]

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号