首页> 外文期刊>Experimental Techniques >An influence of air volume flow rate and temperature set point on performance of inverter split-type air-conditioner
【24h】

An influence of air volume flow rate and temperature set point on performance of inverter split-type air-conditioner

机译:风量流量和温度设定点对变频分体式空调性能的影响

获取原文
获取原文并翻译 | 示例
           

摘要

This paper presents an experimental and analytical study on the inverter split-type air-conditioner for the purpose of energy saving and a proper balance between sensible and latent capacity. Performance of an inverter split-type air-conditioner is investigated at varied refrigerant mass flow rates, air volume flow rates, and set point temperatures. The performance investigated for a 2.54-kW inverter split-type air-conditioner includes cooling capacity, power consumption, the value of coefficient of performance (COP), and equipment sensible heat ratio (SHR). An increase of electrical frequency input to compressor from 34 to 66 Hz results in an increase of cooling capacity by 0.88 kW, a decrease of COP by 0.84, and a decrease of SHR by 0.11. An increase in cooling coil flow rate from 4.14 to 8.2 m 3/min results in an increase in cooling capacity by 0.16 kW, an increase in COP by 0.10, and an increase in SHR by 0.15. An increase of set point temperature from 24 to 26°C results in an increase of the value of COP by 0.13 and a decrease of SHR by 0.03. The study offers guidelines for the application of small-size inverter split-type air-conditioners in hot and humid climates.
机译:本文针对变频分体式空调进行了实验和分析研究,目的是实现节能并在显性和潜性之间达到适当的平衡。研究了在不同的制冷剂质量流量,风量流量和设定点温度下,逆变器分体式空调的性能。对2.54 kW变频分体式空调器进行研究的性能包括制冷量,功耗,性能系数(COP)值和设备显热比(SHR)。输入到压缩机的电频率从34 Hz增加到66 Hz,导致冷却能力提高0.88 kW,COP降低0.84,SHR降低0.11。冷却盘管流量从4.14增加到8.2 m 3 / min导致冷却能力增加0.16 kW,COP增加0.10,SHR增加0.15。设定点温度从24°C升高到26°C,COP值增加0.13,SHR减少0.03。该研究为在炎热和潮湿的气候下使用小型变频分体式空调提供了指南。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号