This paper deals with a dynamic voltage restorer (DVR) characterized by installing the shunt converter at the load side. The DVR can compensate for the load voltage when a voltage sag appears in the supply voltage. An existing DVR requires a large capacitor bank or other energy-storage elements such as double-layer capacitors or batteries. The DVR presented in this paper requires only a small DC capacitor intended for smoothing the DC-link voltage. Moreover, three control methods for the series converter are compared and discussed to reduce the series-converter rating, paying attention to the zero-sequence voltages included in the supply voltage and the compensating voltage. Experimental results obtained from a 200-V, 5-kW laboratory system are shown to verify the viability of the system configuration and the control methods.
机译:本文介绍了一种动态电压恢复器(DVR),其特征在于在负载侧安装了并联转换器。当电源电压中出现电压骤降时,DVR可以补偿负载电压。现有的DVR需要大容量的电容器组或其他储能元件,例如双层电容器或电池。本文介绍的DVR仅需要一个用于平滑直流链路电压的小型直流电容器。此外,比较并讨论了串联转换器的三种控制方法,以降低串联转换器的额定值,同时要注意电源电压和补偿电压中包含的零序电压。显示了从200V,5kW实验室系统获得的实验结果,以验证系统配置和控制方法的可行性。