首页> 外文期刊>International Journal of Refrigeration >Experimental investigation on the performance of the refrigeration cycle using a two-phase ejector as an expansion device
【24h】

Experimental investigation on the performance of the refrigeration cycle using a two-phase ejector as an expansion device

机译:使用两相喷射器作为膨胀装置的制冷循环性能的实验研究

获取原文
获取原文并翻译 | 示例
           

摘要

In the present study, new experimental data on the performance of a never before seen two-phase ejector refrigeration cycle (TPERC) is presented. In this cycle, a two-phase ejector is used as an expansion device. The TPERC enables the evaporator to operate as in a liquid-recirculation system. The results are compared with those of the conventional refrigeration cycle (CRC). The effects of external parameters, i.e., heat sink and heat source temperatures on the system performance are discussed. The results show that the coefficient of performance of the TPERC is higher than that of the CRC over the whole range of experimental conditions. This is due to a higher refrigerant-side heat transfer coefficient in the evaporator, resulting from the higher refrigerant mass flow rate passing through the evaporator. However, the increase becomes relatively smaller as the heat sink temperature increases.
机译:在本研究中,提出了关于前所未有的两相喷射器制冷循环(TPERC)性能的新实验数据。在该循环中,两相喷射器用作膨胀装置。 TPERC使蒸发器能够像液体再循环系统一样运行。将结果与常规制冷循环(CRC)的结果进行比较。讨论了外部参数(即散热器和热源温度)对系统性能的影响。结果表明,在整个实验条件范围内,TPERC的性能系数均高于CRC。这是由于通过蒸发器的较高的制冷剂质量流量导致蒸发器中的较高的制冷剂侧传热系数。但是,随着散热器温度的升高,该升高变得相对较小。