Experimental study on condensation heat transfer and pressure drop in horizontal smooth tube for R1234ze(E), R32 and R410A

机译:R1234ze(E),R32和R410A的水平光管冷凝水传热和压降的实验研究

获取原文
获取原文并翻译 | 示例
           

摘要

Experimental condensation heat transfer and pressure drop of R1234ze(E), trans-1, 3, 3, 3-tetrafluoropropene (trans-CHF=CHCF_3) in a horizontal smooth tube are measured and compared with R32 and the nearly azeotropic HFC refrigerant blend R410A. The effects of mass flux and saturation temperature on heat transfer and pressure drop have been conducted and analyzed. The copper tube with inner diameter of 4.35 mm and length of 3.6 m was used as the test sections. The tests were conducted for mass fluxes varying from 150 to 400 kg (m~(-2) s~(-1)) and the saturation temperature ranging between 35 and 45℃ over the vapor quality range 0.0-1.0. It was found that the experimental heat transfer performance of R1234ze(E) was about 20-45% lower than R32 but 10-30% higher than R410A for saturation temperature 40℃. The experimental results are compared with some well-known existing prediction methods of condensation of pure refrigerant.
机译:测量了水平光滑管中R1234ze(E),反式1、3、3、3-四氟丙烯(trans-CHF = CHCF_3)的实验冷凝热传递和压降,并将其与R32和几乎共沸的HFC制冷剂混合物R410A进行了比较。进行了质量通量和饱和温度对传热和压降的影响分析。内径为4.35 mm,长度为3.6 m的铜管用作测试部分。在蒸气质量范围为0.0-1.0的条件下,对质量通量为150至400 kg(m〜(-2)s〜(-1))和饱和温度在35至45℃的范围进行了测试。结果表明,在40℃的饱和温度下,R1234ze(E)的传热性能比R32低约20-45%,但比R410A高10-30%。将实验结果与一些已知的纯制冷剂冷凝预测方法进行了比较。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号