Refrigerant and airflow maldistribution in fin-and-tube evaporators for residential air-conditioning was investigated with numerical modeling. Fin-and-tube heat exchangers usually have a pre-defined circuitry. However, the objective in this study was to perform a generic investigation of each individual maldistribution source in an independent manner. Therefore, the evaporator and the condenser were simplified to be straight tubes for the purposes of this study. The numerical model of the R410A system, its verification and an investigation of individual maldistribution sources are presented in this paper. The maldistribution sources of interest were: inlet liquid/vapor phase distribution, feeder tube bending and airflow distribution. The results show that maldistribution reduced the cooling capacity and the coefficient of performance of the system. In particular, different phase distribution and non-uniform airflow distribution reduced the performance significantly. Different feeder tube bendings only caused a minor decrease in performance.
机译:利用数值模型研究了用于室内空调的翅片管蒸发器中的制冷剂和气流分布不均。翅片管式热交换器通常具有预定的电路。但是,本研究的目的是以独立的方式对每个单独的不当分布来源进行一般性调查。因此,出于本研究的目的,蒸发器和冷凝器简化为直管。本文介绍了R410A系统的数值模型,它的验证以及对单个不正确分布来源的调查。感兴趣的分布不均的来源是:入口液相/气相分布,进料管弯曲和气流分布。结果表明,分布不均会降低系统的制冷量和性能系数。特别是,不同的相分布和不均匀的气流分布会大大降低性能。不同的进料管弯曲只会导致性能略有下降。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号