Effects of water mal-distribution on thermostatic-expansion-valve (TEV) stability and its controlled two-circuit evaporator performance were investigated experimentally and numerically. 7 sets of water mal-distribution were obtained with Circuit 2 water percentage (F-2) from 36.9% to 9.1%. Results showed that the TEV control-loop was stable with F-2 from 36.9% to 27.0%, and the overall evaporator capacity decreased by 3.4%. However, hunting occurred with F-2 from 27.0% to 9.1% due to the evaporator outlet superheat smaller than the TEV minimal stable signal (MSS), hence system parameters such as evaporator pressures and temperatures oscillated over time. Hunting introduced a sharp decrease in the refrigerant flowrate to the evaporator, thus the overall evaporator capacity decreased by 14.1%. With water mal-distribution rate increased, the decrease in overall evaporator capacity was mainly attributed to Circuit 2 with smaller overall heat transfer coefficient. (C) 2014 Elsevier Ltd and IIR. All rights reserved.
机译:实验和数值研究了水分配不均对恒温膨胀阀(TEV)稳定性及其受控的二回路蒸发器性能的影响。在第2回路水百分比(F-2)从36.9%到9.1%的情况下,获得了7套水分配不均。结果表明,TEV控制回路在F-2从36.9%稳定到27.0%时是稳定的,而蒸发器的总容量下降了3.4%。但是,由于蒸发器出口过热小于TEV最小稳定信号(MSS),F-2的波动从27.0%降至9.1%,因此系统参数(例如蒸发器压力和温度随时间波动)会发生变化。亨廷顿(Hunting)导致流向蒸发器的制冷剂流量急剧减少,因此蒸发器的整体容量下降了14.1%。随着水分配不均率的增加,蒸发器总容量的下降主要归因于回路2的总传热系数较小。 (C)2014 Elsevier Ltd和IIR。版权所有。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号