The objective of this study is to investigate the heat transfer characteristics of discrete plate finned-tube heat exchangers with large fin pitches. Thirty-four heat exchangers were tested with variations of fin pitches, the number of tube rows, fin alignment, and vertical fin space. The j-factor of the discrete plate finned-tube exchanger was analyzed as a function of coil geometry and then compared with that of the continuous plate finned-tube heat exchanger. For fin pitches of 7.5-15 mm, the j-factors of the discrete plate finned-tube heat exchangers were 6.0-11.6% higher than those of the continuous plate finned-tube heat exchangers. Two separate correlations for the j-factor were developed for the inline and the staggered fin alignment in the discrete plate finned-tube heat exchangers to predict the measured data within a relative deviation of 2.9%.
机译:这项研究的目的是研究大翅片节距的离散板翅片管式换热器的传热特性。测试了34个换热器的翅片间距,管排数,翅片对准和垂直翅片空间的变化。分析了离散板翅片管式换热器的j因子与线圈几何形状的关系,然后将其与连续板翅片管式换热器的j因子进行了比较。对于7.5-15 mm的翅片节距,分立板翅片管式换热器的j因子比连续板翅片管式换热器的j因子高6.0-11.6%。针对离散板翅片管式换热器的直列式和交错式翅片对准建立了j因子的两个独立相关性,以在2.9%的相对偏差内预测测量数据。