Combined Cooling, Heating, and Power (CCHP) systems with cool thermal storage can provide an appropriate energy supply for data centers. In this work, we evaluate the CCHP system performance under two different operation strategies, i.e., following thermal load (FTL) and following electric load (FEL). The evaluation is performed through a case study by using TRNSYS software. In the FEL system, the amount of cool thermal energy generated by the absorption chillers is larger than the cooling load and it can be therefore stored and reused at the off-peak times. Results indicate that systems under both operation strategies have advantages in the fields of energy saving and environmental protection. The largest percentage of reduction of primary energy consumption, CO2 emissions, and operation cost for the FEL system, are 18.5%, 37.4% and 46.5%, respectively. Besides, the system performance is closely dependent on the equipment selection. The relation between the amount of energy recovered through cool thermal storage and the primary energy consumption has also been taken into account. Moreover, the introduction of cool thermal storage can adjust the heat to power ratio on the energy supply side close to that on the consumer side and consequently promote system flexibility and energy efficiency. (C) 2016 Elsevier Ltd. All rights reserved.
机译:结合了冷,热和电(CCHP)系统以及冷蓄热装置的系统可以为数据中心提供适当的能源供应。在这项工作中,我们在两种不同的操作策略(即跟随热负载(FTL)和跟随电负载(FEL))下评估CCHP系统性能。使用TRNSYS软件通过案例研究进行评估。在FEL系统中,吸收式制冷机产生的冷热能量大于制冷负荷,因此可以在非高峰时间进行存储和再利用。结果表明,两种运行策略下的系统在节能环保方面均具有优势。 FEL系统一次能源消耗,CO2排放和运营成本减少的最大比例分别为18.5%,37.4%和46.5%。此外,系统性能与设备选择密切相关。还考虑了通过冷蓄热回收的能量与一次能源消耗之间的关系。而且,引入冷蓄热器可以调节能量供应侧的热电比接近消费者侧的热电比,从而提高系统的灵活性和能源效率。 (C)2016 Elsevier Ltd.保留所有权利。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号