Calculation for the lightning surge current distribution in reinforced concrete building caused by direct strikes

机译:直接罢工钢筋混凝土建筑雷电浪涌电流分布的计算

获取原文
获取原文并翻译 | 示例
           

摘要

Lightning surges appear in the telecommunication cables, power lines, and grounding lines when the direct lightning is stroke telecommunication center building. These might be a cause of trouble for telecommunications equipment. We should study the current distribution in the building due to the direct stroke, and observe the lightning surge current distribution in order to improve the immunity of telecommunication system. In this report, the beams and pillars in building were assumed by the equivalent radius column conductors, which have same surface area of the complex reinforced concrete beams and pillars. The building structure was modeled lattice structure with the column conductors. The lightning surge current at the beams and pillars were calculated with this model, and the results are compared with the observed results. The deviation between calculated and observed value is around 200%. Further study to reduce calculation error is needed to develop the effective model for analysis.
机译:当直接闪电是笔划电信中心建筑时,电信电缆,电源线和接地线出现在电信电缆,电源线和接地线上。这些可能是电信设备问题的原因。我们应该在直接行程中研究建筑物的当前分布,并观察闪电浪涌电流分布,以提高电信系统的免疫力。在本报告中,相当半径柱导体假设建筑物中的梁和支柱,其具有相同的复合钢筋混凝土梁和支柱的表面积。建筑结构用柱导体模拟晶格结构。通过该模型计算梁和支柱处的雷电浪涌电流,并将结果与​​观察结果进行比较。计算和观察值之间的偏差约为200%。需要进一步研究以减少计算错误来开发有效的分析模型。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号