The TAPS 4 DPHS-PCS system was commissioned in August 2004. The system was successfully used during hot-conditioning and pressurizer performance tests. The system has performed exceedingly well during several stages of power operation of TAPS 4. During load throwoff tests carried out at 50 percent and 90 percent full power, creating simultaneous severe transients in all the processes, DPHS-PCS regulated all the six processes very well. The documents submitted to AERB by TAPS 4 station authorities states that, the performance of DPHS-PCS has been very good. Primary coolant pressure has been maintained well within the small range of 100 kg/sq.cm. during various transients like turbine trips, load rejection and reactor trips. With the system experiencing several transients, it has never shown any indication of tending towards trip set points of PHT low or high pressure. The TAPS 3 DPHS-PCS was also successfully commissioned in November 2005.
机译:TAPS 4 DPHS-PCS系统于2004年8月投入使用。该系统已成功用于热调节和增压器性能测试。该系统在TAPS 4的电源运行的几个阶段中表现都非常出色。在以50%和90%的全功率进行负载甩负荷测试期间,在所有过程中同时产生严重的瞬变,DPHS-PCS很好地调节了所有六个过程。 TAPS 4站点主管部门提交给AERB的文件指出,DPHS-PCS的性能非常好。一次冷却剂压力一直保持在100 kg / sq.cm的小范围内。在诸如涡轮机跳闸,甩负荷和电抗器跳闸之类的各种瞬变过程中。随着系统经历几次瞬变,它从未显示出趋向于PHT低压或高压跳闸设定点的任何迹象。 TAPS 3 DPHS-PCS也于2005年11月成功调试。