The introduction of high voltage direct current (HVdc)-systems based on voltage source converters (VSC) within the ac transmission system enables new operational strategies. Fast VSC set-point adaptations in post-contingency scenarios can re-establish a secure state of the overall system. However, these corrective actions require a reliable activation and global coordination, especially of the HVdc-system and its dc voltage control. A comprehensive approach addressing these requirements is presented in this work. The approach is divided into three main modules. During online operation, critical contingency events are identified based on local measurements. An expansion of the local converter control enables an activation of suitable corrective actions to be pre-determined by a corrective security constrained optimal power flow.
机译:基于AC传输系统内的电压源转换器(VSC)的高压直流(HVDC)-Systems的引入可实现新的操作策略。 在应急场景中快速VSC设置点调整可以重新建立整个系统的安全状态。 但是,这些纠正措施需要可靠的激活和全局协调,特别是HVDC系统及其直流电压控制。 在这项工作中提出了一种解决这些要求的综合方法。 该方法分为三个主要模块。 在在线操作期间,基于本地测量来识别临界应急事件。 本地转换器控制的扩展使得能够激活采用校正安全约束的最佳功率流预先确定的合适的校正动作。