Corrosion failure analysis of galvanized steel pipes in a closed water cooling system

机译:封闭水冷却系统中镀锌钢管的腐蚀故障分析

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

AbstractThe present study is focused on the corrosion failure analysis of a water cooling system serving a polyethylene terephtalate (PET) preform molding plant.Piping mainly located both after the water pretreatment and in the injection molding machines was affected by an extensive corrosion phenomenon and several leakages of coolant occurred, involving the risk of loss of functionality of the whole plant.The main problem detected in closed cooling circuits was a marked modification of the water chemistry and a great amount of metal ions leading to recurring fouling of the inner surfaces of molds and cooling channels.Analysis of water flowing in the closed cooling circuit operating at 6°C revealed a very high amount of metals in the flowing water and in the sediment (zinc and iron). Moreover the water pH was slightly acidic. Data were compared with water from supply well.Preliminary electrochemical characterization was carried out on galvanized steel pipe, in order to evaluate the aggressiveness of water both from the cooling circuits and from the supply wells.The results of laboratory analysis together with the scrutiny of the available technical documentation showed that the damage of the plant was the consequence of an inadequate plant management, mainly for what concerns materials selection and water chemical treatment.Highlights?Corrosion failure analysis of a cooling system serving a PET preform molding plant.?Failure of galvanized steel piping after seven years.?Analysis of the water from the supply wells and cooling circuits.?Inadequate plant management in terms of material selection and water chemical treatment.]]>
机译:<![cdata [ 抽象 本研究专注于提供聚对苯二甲酸乙二醇酯(PET)预制件的水冷却系统的腐蚀失效分析成型厂。 管道主要位于水预处理和注塑机中的既受到广泛的腐蚀现象的影响发生了几种冷却剂泄漏,涉及整个植物功能丧失的风险。 在闭合冷却中检测到的主要问题电路是水化学的显着改变,以及大量的金属离子,导致内表面的反复污染模具和冷却通道的es。 在6°C工作中运行的闭合冷却电路中流动的水分显示出非常高流动水和沉积物(锌和铁)中的金属量。此外,水pH略微酸性。将数据与来自供应良好的水进行比较。 初步电化学表征在镀锌钢管上进行,以评估来自冷却电路和供应井的水的侵略性。 实验室分析结果与审查的审查结果可用技术文件表明,该植物的损害是植物管理不足的结果,主要是涉及材料选择和水化学处理的内容。 亮点 用于PET预制件成型工厂的冷却系统的腐蚀故障分析。 七年后镀锌钢管失效。 从供应井和冷却电路的水分析。 在材料选择和水化学处理方面的工厂管理不足。 < / ce:列表 - 项目> ]]>

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号