首页> 外文期刊>International Journal of Ventilation >Experimental investigation on night sky radiant cooling performance of duct-type heat exchanger
【24h】

Experimental investigation on night sky radiant cooling performance of duct-type heat exchanger

机译:导管式热交换器夜空辐射性能的实验研究

获取原文
获取原文并翻译 | 示例
           

摘要

Night sky radiant cooling is one of such promising natural techniques that can be worth a high recommendation. In this study, a novel design of night sky radiation heat exchanger is proposed, and its influencing factors were evaluated by the experimental investigations. The night sky radiant cooling performance of duct-type heat exchanger under different surface material and weather conditions were conducted by case study. The results show that the temperature differences between the inlet and outlet air of the duct-type heat exchanger under the heat exchanger surface painted and unpainted conditions were about 6.8 and 2.3 degrees C, respectively. The temperature differences between the inlet and outlet air under the weather conditions of clear sky, cloudy sky and overcast sky were averagely 6.8, 4.9 and 4.4 degrees C, respectively. It can be concluded that the surface material emissivity plays an essential role on the cooling performance of night sky radiation heat exchanger.
机译:夜空辐射冷却是如此有希望的自然技术之一,这是值得高的推荐。 在本研究中,提出了一种新颖的夜空辐射热交换器设计,通过实验研究评估其影响因素。 通过案例研究进行了不同表面材料和天气条件下的管道式热交换器的夜空辐射性能。 结果表明,热交换器表面下的管式热交换器的入口和出口之间的温度差异分别为约6.8和2.3摄氏度。 晴朗的天空,多云天空和阴天天气下的天气条件下的入口和出口空气之间的温差分别为6.8,4.9和4.4摄氏度。 可以得出结论,表面材料发射率在夜空辐射热交换器的冷却性能上起着重要作用。