This study presents extensive experimental measurements in a modern Finnish ice rink arena including temperature, relative humidity, carbon dioxide, air speed, air flow and pressure difference measurements in addition to smoke tests. Furthermore, the air exchange rate (ACH), air-exchange efficiency, and mixing factor were calculated. The main aim was to determine ventilation effectiveness, vertical stratification of the air and how commonly re-circulation can be used in a modern ice rink arena representing common practice. Results show that re-circulation of return air was virtually continuous and in normal operating conditions the outdoor air fraction of the supply air was only 3.7% corresponding to ACH of 0.03 1/h. The ceiling distributed mixing ventilation was not able to mix the whole volume sufficiently, leading to two imperfectly mixed zones with an average air-exchange efficiency of 39% in the lower zone, corresponding to a mixing factor of 1.7.
机译:本研究在现代芬兰冰溜冰场中提供了广泛的实验测量,包括温度,相对湿度,二氧化碳,空气速度,空气流量和压力差测量以及烟雾测试。 此外,计算了空气汇率(ACH),空气交换效率和混合因子。 主要目的是确定空气的通风效果,垂直分层以及常见的循环如何用于代表普通实践的现代溜冰场。 结果表明,返回空气的再循环几乎是连续的,在正常操作条件下,供应空气的室外空气分数仅为3.7%,对应于0.03 1 / h。 天花板分布式混合通风不能充分地混合整个体积,导致两个不完全混合的区域,平均空气交换效率为下部区域39%,对应于1.7的混合因子。