首页> 外文期刊>Computational intelligence and neuroscience >Fuzzy Inference System Approach for Locating Series, Shunt, and Simultaneous Series-Shunt Faults in Double Circuit Transmission Lines
【24h】

Fuzzy Inference System Approach for Locating Series, Shunt, and Simultaneous Series-Shunt Faults in Double Circuit Transmission Lines

机译:双电路输电线路定位串联,分流和同声系列分流故障的模糊推理系统方法

获取原文
获取原文并翻译 | 示例
       

摘要

Many schemes are reported for shunt fault location estimation, but fault location estimation of series or open conductor faults has not been dealt with so far. The existing numerical relays only detect the open conductor (series) fault and give the indication of the faulty phase(s), but they are unable to locate the series fault. The repair crew needs to patrol the complete line to find the location of series fault. In this paper fuzzy based fault detection/classification and location schemes in time domain are proposed for both series faults, shunt faults, and simultaneous series and shunt faults. The fault simulation studies and fault location algorithm have been developed usingMatlab/Simulink. Synchronized phasors of voltage and current signals of both the ends of the line have been used as input to the proposed fuzzy based fault location scheme. Percentage of error in location of series fault is within 1% and shunt fault is 5% for all the tested fault cases. Validation of percentage of error in location estimation is done using Chi square test with both 1% and 5% level of significance.
机译:报告了许多方案进行分流故障定位估计,但到目前为止还没有处理串联或开放导体故障的故障定位估计。现有数值继电器仅检测开放导体(系列)故障并指示故障阶段,但它们无法定位串联故障。维修人员需要巡逻完整的线路以找到串联故障的位置。在本文的基础故障检测/分类和定位方案中,提出了两种故障,分流故障和同时系列和分流故障。使用Matlab / Simulink开发了故障仿真研究和故障定位算法。该线路两端的电压和电流信号的同步相位已被用作所提出的基于模糊的故障定位方案的输入。所有测试故障情况下,串联故障位置的误差率在1%内,分流故障为5%。使用Chi Square测试验证位置估计中的误差百分比,其具有1%和5%的显着性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号