Analysis of non-symmetrical operating conditions of 0,38 kV rural networks

机译:0,38 kV农村电网非对称运行条件分析

获取原文
获取原文并翻译 | 示例
       

摘要

Formulae are given for determining approximate values of positive-sequence currents, negative-sequence currents and zero-sequence currents by using the values of three phase currents. Calculations of a typical 0,38 kV rural network withtransformer windings connected in star-star-zero and star-zigzag-zero are carried out. It is shown that in contrast to the negative-sequence coefficient of voltages the values of the zero-sequence coefficient of voltages when transformerwindings are connected in star-star-zero largely exeed the ones established by the State StandardГOCT 13109-87. Power losses are less in a network with transformers connected in star-zigzag-zero.
机译:给出了用于通过使用三相电流的值来确定正序电流,负序电流和零序电流的近似值的公式。进行了一个典型的0.38 kV农村电网的计算,该农村电网的变压器绕组分别连接在“星-星-零”和“星-之字形-零”中。结果表明,与电压的负序系数相反,在《星-星-零》中连接变压器绕组时电压的零序系数的值大大超过了国家标准OCT 13109-87规定的值。 。在将变压器连接到“ star-zigzag-zero”中的网络中,功率损耗较小。