首页> 外文期刊>電子情報通信学会技術研究報告. 環境電磁工学. Electromagnetic Compatibility >Observation results of lightning surge current induced at AC mains line for access network equipment installed outdoors, and a lightning surge immunity test
【24h】

Observation results of lightning surge current induced at AC mains line for access network equipment installed outdoors, and a lightning surge immunity test

机译:在室外安装的接入网设备的交流电源线上感应的雷电浪涌电流的观察结果以及雷电浪涌抗扰度测试

获取原文
获取原文并翻译 | 示例
       

摘要

As access network equipment installed outdoors has increased in performance and decreased in power, the likelihood of lightning surges induced in the access system has also increased. Power unit malfunctions occur frequently due to lightning surge current induced on the AC mains line. We observed the lightning surge current and the waveform characteristics, whose half time values are longer than existing recommendations, and the occurrence probability, which is 30 times greater than on telecommunication lines. Based on the observation results, this paper proposes a new lightning surge immunity test for access network systems.
机译:随着安装在室外的接入网络设备的性能提高和功率降低,接入系统中引发的雷电浪涌的可能性也增加了。由于交流电源线上感应的雷电浪涌电流,经常导致功率单元故障。我们观察到雷电浪涌电流和波形特性(其半衰期值比现有建议值更长)和出现概率(比电信线路大30倍)。基于观察结果,本文提出了一种新的针对接入网系统的雷电浪涌抗扰度测试。