Modular Design for a Single-Phase Manifold Mini/Microchannel Cold Plate

机译:单相流道微型/微通道冷板的模块化设计

获取原文
获取原文并翻译 | 示例
           

摘要

The present work is related to the design of a manifold mini/microchannel heat sink with high modularity and performance for electronics cooling, utilizing two well established (i.e., jet impingement and channel flow) cooling technologies. A manifold system with cylindrical connection tubes and tapered inserts is designed for uniform coolant distribution among different channels and easy manufacturing of the whole cooling device. The design of the insert provides freedom to manipulate the flow structure within each manifold section and balance the cooling performance and required pumping power for the cold plate. Due to the optimized tapered shape of the insert inlet branches, fluid flows more uniformly through the entire heat sink fin region leading to uniform heat sink base temperatures. Extending the design of the heat sink fin structure from the mini to micro-scale, and doubling of the number of insert inlet/outlet branches, results in an 80% increase in the cooling performance, from 30 kW/(m~2·K) to 54 kW/(m~2·K), with only a 0.94 kPa added pressure drop penalty. The present cold plate design also provides flexibility to assemble manifold sections in different configurations to reach different flow structures, and thus different cooling performance, without redesign. The details of the modular manifold and possible configurations of a cold plate comprising three manifold sections are shown herein. A conjugate flow and heat transfer three-dimensional (3D) numerical model is developed for each configuration of the cold plate to demonstrate the merits of each modular design. Parallel flow configurations are used to satisfy a uniform cooling requirement from each module, and it is shown that "U-shape" parallel flow "base" configuration cools the modules more uniformly than a "Z-shape" flow pattern due to intrinsic pressure distribution characteristics. A serial fluid flow configuration requires the minimum coolant flow rate with a gradually increasing device temperature along the flow direction. Two mixed (i.e., parallel + serial flow) configurations achieve either cooling performance similar to the U-shape configuration with slightly more than half of the coolant flow rate, or cooling of a specific module to a much lower temperature level. Generally speaking, the current cold plate design significantly extends its application to different situations with distinct cooling requirements.
机译:本工作涉及利用两种成熟的(即射流冲击和通道流动)冷却技术设计具有高模块性和电子冷却性能的歧管微型/微通道散热器。具有圆柱形连接管和锥形插件的歧管系统设计用于在不同通道之间均匀分配冷却液,并易于制造整个冷却装置。插入件的设计提供了在每个歧管部分内操纵流动结构,平衡冷却性能和冷却板所需的泵送功率的自由度。由于刀片入口分支的最佳锥形形状,流体更均匀地流过整个散热片区域,从而导致均匀的散热片基础温度。将散热片结构的设计从微型扩展到微型,并且插入件入口/出口分支的数量增加一倍,从而使冷却性能从30 kW /(m〜2·K)提高了80% )至54 kW /(m〜2·K),仅增加0.94 kPa的压降损失。本冷却板的设计还提供了灵活性,可以在不进行重新设计的情况下以不同的构造组装歧管段以达到不同的流动结构,从而达到不同的冷却性能。这里示出了模块化歧管的细节以及包括三个歧管部分的冷板的可能构造。针对冷板的每种配置开发了共轭流动和传热三维(3D)数值模型,以演示每种模块化设计的优点。平行流配置用于满足每个模块的均匀冷却要求,并且显示出由于固有压力分布,“ U形”并行流“基本”配置比“ Z形”流模式更均匀地冷却了模块特征。串行流体流动配置要求最小的冷却剂流速,并沿着流动方向逐渐提高设备温度。两种混合(即并行+串行流动)配置可达到类似于U形配置的冷却性能,但冷却剂流量仅略多于一半,或将特定模块冷却到更低的温度水平。一般而言,当前的冷板设计将其应用显着扩展到具有不同冷却要求的不同情况。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号