摘要

Evaluation of discharge gas cooling system of a natural gas compressor station was studied. Scale deposition potential and corrosion forming tendencies of the cooling water were monitored. Plant operating at high Holding Time Index contributed towards increased scale forming potential of cooling water. Corrosion data analysis showed slightly high rate of corrosion of cooling water that may be due to improper management of acid dosing in the system. Absence of side stream filtration unit might have supported increased turbidity in the system that helped increased growth of microbial colonies in the water. Cooling water quality standards did not support in keeping balance between corrosive and scale forming potential of the circulating water. Therefore, improved limits of cooling water quality standards have been suggested in this work.
机译:研究了天然气压缩机站排气冷却系统的评估。监测冷却水的水垢沉积电位和腐蚀形成趋势。在高保温时间指数下运行的工厂有助于增加冷却水的水垢形成潜力。腐蚀数据分析表明,冷却水的腐蚀速率略高,这可能是由于系统中酸液管理不当所致。缺少侧流过滤单元可能有助于增加系统中的浊度,从而有助于增加水中微生物菌落的生长。冷却水质量标准不支持在循环水的腐蚀性和结垢潜力之间保持平衡。因此,在这项工作中提出了改善冷却水质量标准的限制。