GIS (Gas Insulated Switchgear) is used in electric power system to insure non conductivity, breaking capacity and operating reliability. In the present study, dynamic analysis on the closing resistors of the GIS has bees carried out by the commercial dynamic analysis code COSMOS MOTION and 3-D modeling program SOLID WORKS In order to find the minimum value of chatter vibration of closing resistors, the motion of moving and fixed resistor parts of closing resistors were simulated by varying the spring constant, the damping coefficient and the mass of moving and fixed resistor parts. The simulated results were compared with experimental results. The application of the results could reduce chatter vibration of closing resistors of the GIS These data are also useful on the development of future model GIS with minimum chatter vibration for the determinations of the spring constant, the damping coefficient and mass of a moving part.
机译:GIS(气体绝缘开关设备)用于电力系统中,以确保不导电,分断能力和操作可靠性。在本研究中,通过商业动态分析代码COSMOS MOTION和3-D建模程序SOLID WORKS对GIS的闭合电阻器进行了动态分析,以便找到闭合电阻器的颤动振动的最小值。通过改变弹簧常数,阻尼系数和移动和固定电阻器部件的质量,模拟了闭合电阻器的移动和固定电阻器部件的数量。仿真结果与实验结果进行了比较。结果的应用可以减少GIS闭合电阻器的颤动振动。这些数据对于确定最小颤动振动的未来模型GIS的确定弹簧系数,阻尼系数和运动部件的质量也很有用。