首页> 外文期刊>VGB KraftwerksTechnik >Test of different measures for the prevention of scaling in the cooling system of Grohnde Nuclear Power Plant
【24h】

Test of different measures for the prevention of scaling in the cooling system of Grohnde Nuclear Power Plant

机译:格罗德核电站冷却系统防止结垢的不同措施的测试

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

In the cooling system of the Grohnde Nuclear Power Plant, heavy calcium carbonate precipitations have occurred in the turbine condenser and in the cooling tower since 1994. Those precipitations cause performance losses and high cleaning costs. Reasons for the intensified precipitation are apparently the biologically upgraded water quality of the river Weser, as well as specific operational conditions of the cooling system (partial recirculation of cooling water). It was noticed that the formation of calcium carbonate deposits occurred within a limited period of less than two weeks in May. The calcium precipitation was that strong during this time that it could not be stopped despite the immediate application of corundum cleaning balls in the tube cleaning system.
机译:自1994年以来,在格罗德核电站的冷却系统中,在涡轮冷凝器和冷却塔中出现了重质碳酸钙沉淀。这些沉淀会导致性能损失和高昂的清洁成本。降水增加的原因显然是韦瑟河的生物水质得到了改善,以及冷却系统的特定运行条件(冷却水的部分再循环)。值得注意的是,碳酸钙沉积物的形成发生在5月不到两周的有限时间内。在这段时间内,钙沉淀非常强烈,尽管在管清洗系统中立即使用了刚玉清洗球,但仍无法停止。