Point-of-use filtration method for the prevention of fungal contamination of hospital water.

机译:使用点过滤方法可防止对医院用水的真菌污染。

获取原文
获取原文并翻译 | 示例
           

摘要

Published data implicate hospital water as a potential source of opportunistic fungi that may cause life-threatening infections in immunocompromised patients. Point-of-care filters are known to retain bacteria, but little is known about their efficacy in reducing exposure to moulds. We investigated the effect of point-of-use filters (Pall-Aquasafe) on the level of contamination of Aspergillus fumigatus and other filamentous fungi. The point-of-use filters were applied to several outlets (taps and showers) on the paediatric bone marrow transplantation (BMT) unit of the National Hospital in Oslo, Norway. In addition the efficacy was investigated using a test rig. The laboratory experiments showed that the filters were highly effective in reducing the number of colony-forming units for a period of at least 15 days. In the BMT unit the filters eliminated the fungi from the water on day 1 but due to particles present in the water the filters occluded, which prevented further evaluations. Our results show that point-of-use filtration might be an effective preventive measure to eliminate filamentous fungi at individual points of water use, thereby reducing patients' exposure.
机译:公开的数据暗示医院用水是机会真菌的潜在来源,可能会在免疫功能低下的患者中造成威胁生命的感染。现场护理过滤器可保留细菌,但对于减少霉菌暴露的功效知之甚少。我们调查了使用点过滤器(Pall-Aquasafe)对烟曲霉和其他丝状真菌污染水平的影响。使用点过滤器已应用于挪威奥斯陆国家医院小儿骨髓移植(BMT)单元的多个出口(水龙头和淋浴器)。另外,使用试验台对功效进行了研究。实验室实验表明,过滤器在减少菌落形成单位的数量上至少15天非常有效。在BMT装置中,过滤器在第1天就从水中消除了真菌,但由于水中存在颗粒,过滤器被堵塞,这妨碍了进一步评估。我们的结果表明,使用点过滤可能是在各个用水点消除丝状真菌的有效预防措施,从而减少了患者的暴露。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号