首页> 外文期刊>Practical Metallography >An Investigation of Ant-Nest Corrosion caused by the Leakage of a Copper Tube - Finned Heat Exchanger of an Air Conditioning Unit
【24h】

An Investigation of Ant-Nest Corrosion caused by the Leakage of a Copper Tube - Finned Heat Exchanger of an Air Conditioning Unit

机译:空调机翅片式换热器泄漏引起的蚁巢腐蚀研究

获取原文
获取原文并翻译 | 示例
           

摘要

Leakages often occur in the copper tube finned heat exchangers of cooling and air conditioning units, the dimensions of which are on the microscopic scale thus making the location and cause very difficult to determine. In the case presented here the leakages found were located using a Helium leak detector. After removing the fins of the heat exchanger, because the points of failure were not visible to the naked eye, a dye penetrant test was carried out on the affected area (Penetrations test or PT), which led to the discovery of three very small indications on one section of the tube. Subsequent microscopic laboratory examination revealed the cause to be -microscopically small holes in the wall of the tube caused by corrosion through from the internal surface of the coolant side of the tube. The corrosion mechanism was identified as Formicary Corrosion otherwise referred to as Ant-Nest Corrosion. For this type of corrosion to occur, which according to the specialist literature is often found in Cooling or Air Conditioning units, an aqueous electrolyte or electrolytic film containing Carbonic acid and Oxygen is required which can lead to damage occurring within weeks to months. In the case described in this article, the unintentional ingress of an aqueous oxygenated acidic solution of Glycol into the heat exchanger was most probably responsible for the damage.
机译:泄漏通常发生在冷却和空调单元的铜管翅片式换热器中,其尺寸在微观尺度上,因此使其位置非常难以确定。在此处介绍的情况下,使用氦气检漏仪定位发现的泄漏。拆下热交换器的散热片后,由于肉眼看不见失效点,因此在受影响区域进行了渗透测试(渗透测试或PT),从而发现了三个非常小的迹象在管的一部分上。随后的显微镜实验室检查表明,原因是由于从管冷却剂侧的内表面穿透腐蚀而在管壁上形成了微小的孔。腐蚀机理被确定为蚁群腐蚀,否则称为蚁巢腐蚀。为了发生这种类型的腐蚀,根据专业文献经常在冷却或空调设备中发现这种腐蚀,需要含有碳酸和氧气的水性电解质或电解质膜,这可能导致数周至数月内发生损坏。在本文所述的情况下,乙二醇的含氧酸性水溶液无意进入热交换器的原因很可能是这种损坏。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号