Water and energy conservation for a counterflow cooling tower using UV light disinfection and variable speed fan

机译:使用紫外线消毒和变速风扇的逆流冷却塔的节水节能

获取原文
获取原文并翻译 | 示例
           

摘要

The present study proposes a new water and energy conservation method for a counterflow cooling tower by using UV light disinfection and variable speed fan. In the proposed approach, the constant speed tower fan was modified to become a variable speed fan by installing an inverter on the fan's motor such that the air flow rate of the cooling tower could be reduced to properly match the partial load operation. Furthermore, a by-pass loop with microfilters and UV lights was also added to our test rig to investigate the elimination effectiveness of tower-related bacteria and to reduce the blowdown loss. The experimental results reveal that for 50% load tests, the energy savings was about 76% and the overall water saving was about 23%. Moreover, from our tests we found that with a daily one-hour disinfection, the population of bacteria can be greatly suppressed to far below infection levels, and an increase in water conservation can be achieved. In addition, the possibility of human infection by bacteria originating from cooling towers should thus be greatly reduced.
机译:本研究提出了一种采用紫外线消毒和变速风扇的逆流冷却塔节水节能新方法。在提出的方法中,通过在风扇的电动机上安装逆变器,将恒速塔式风扇修改为变速风扇,从而可以降低冷却塔的空气流量,以适当地匹配部分负荷运行。此外,我们的试验台上还增加了带有微滤器和紫外线灯的旁路回路,以研究与塔相关的细菌的清除效果并减少排污损失。实验结果表明,对于50%的负载测试,节能量约为76%,总节水量约为23%。此外,从我们的测试中我们发现,每天进行一小时的消毒,可以将细菌数量大大抑制到远低于感染水平,并且可以提高节水率。此外,因此应大大降低人为感染来自冷却塔的细菌的可能性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号