Energy Conservation Using Variable-speed Chilled Water Pumps for Single-loop Chilled Water Systems with Fan-coil Units

机译:带风扇盘管装置的单回路冷冻水系统,使用变速冷冻水泵进行节能

获取原文
获取原文并翻译 | 示例
       

摘要

This article addresses the need to reduce energy consumption by chilled water pumps in air conditioning systems. In particutar, this article considers the use of variable-speed pumping systems. Many office buildings in China utilize air conditioning systems with fan-coil units (FCUs) and a primary/secondary chilled water system without secondary pumps. The simulated air conditioning system performance analysis showed that the single-loop chilled water system with variable-speed chilled water pumps could be used in most office buildings where the cooling loads were synchronized to save energy. Installation of the new systems in two office buildings reduced the energy consumption of the chilled-water pumps by almost 50 percent.
机译:本文解决了通过空调系统中的冷冻水泵降低能耗的需求。特别是,本文考虑了变速泵系统的使用。中国的许多办公大楼都使用带有风机盘管单元(FCU)的空调系统和不带辅助泵的一次/二次冷却水系统。模拟的空调系统性能分析表明,带有变速冷水泵的单回路冷水系统可用于大多数办公楼,在这些办公楼中,冷却负荷是同步的,以节省能源。在两座办公楼中安装新系统后,将冷水泵的能耗降低了近50%。