摘要

Fire detection experiments in a road traffic tunnel were performed in the Runehamar test tunnel 5th-8th March 2007. The Runehamar test tunnel is a full profile road traffic tunnel, 1.65 km long, located outside Andalsnes, Norway. The goal was to examinate smoke and heat detection systems to determinate what kind of principle best suited for detecting a fire in an early stage. The systems were tested during small Heptane pool fires, varying between 0.16 m~2 and 1 m~2, giving heat release rates from 0.2 MW to 2.4 MW accordingly, and one car fire of about 3-5 MW, and with wind conditions varying from 1.1 ms~(-1) to 1.6 m s~(-1). The size of the fires, were designed to be in the range from impossible to difficult to detect. The results were conclusive. Earliest detection of a car fire, fire starts inside, was by smoke detection given fixed limits (3000 μg m~(-3)). With open pool fires, or immediate flames, continues fibre optical heat detection systems was faster given the limits 3 ℃/4 min.
机译:道路交通隧道的火灾探测实验是在2007年3月5日至8日在Runehamar测试隧道中进行的。Runehamar测试隧道是一条全长1.65公里的完整型道路交通隧道,位于挪威安达涅斯郊外。目的是检查烟雾和热探测系统,以确定最适合早期探测火灾的原理。该系统在庚烷池小火中进行了测试,小火在0.16 m〜2和1 m〜2之间变化,相应地释放热量的范围从0.2 MW到2.4 MW,一次汽车着火大约3-5 MW,并且风况变化从1.1毫秒〜(-1)到1.6毫秒〜(-1)。火灾的大小设计为从不可能到难以发现。结果是结论性的。最早的汽车起火是在指定的极限(3000μgm〜(-3))下通过烟雾探测开始的。在开池或明火的情况下,在极限温度为3℃/ 4分钟的情况下,继续进行光纤热探测系统会更快。