首页> 外文期刊>Tunnelling and underground space technology >Performance of a spray system in a full-scale tunnel fire test
【24h】

Performance of a spray system in a full-scale tunnel fire test

机译:喷雾系统在全面隧道火灾测试中的性能

获取原文
获取原文并翻译 | 示例
       

摘要

In recent years, water spray systems have been accepted for protection of long tunnels in Taiwan. This research conducted two full scale tunnel fire experiments using 6 m(2) pool fire of heptane while data from one test is presented in this paper; the ceiling could reach 1022 degrees C under free burn. If a tunnel with spray nozzles operating at a pressure of 3.43 bar and a water flow rate of 3601pm were installed every 5 m in a 50 m range for a 6 m(2) pool fire, not only could the temperature directly above the fire be lowered to below 500 degrees C within 30 s, the temperature of the other ceiling area would also be lowered below 300 degrees C and the heat flux would be lowered below 1 kW/m(2), therefore preventing subsequent fire spread. Moreover, the visibility of the fire returned to above 25 m after 150 s. This newly designed spray system can be installed on one side wall under simple maintenance without the need to shut down the tunnel, while the water can also spray to another wall to provide adequate wall cooling for tunnel protection. It can be effectively applied to rescue and protection in tunnels.
机译:近年来,喷水系统已被接受用于保护台湾的长隧道。这项研究使用6 m(2)的庚烷池火进行了两次全面的隧道着火实验,同时给出了一项测试的数据。在自由燃烧下,天花板可以达到1022摄氏度。如果在6 m(2)游泳池着火的情况下,在50 m范围内每5 m安装了一个具有以3.43 bar的压力运行且水流量为3601pm的喷嘴的隧道,那么不仅火焰正上方的温度会在30 s内降至500摄氏度以下时,另一个天花板区域的温度也将降至300摄氏度以下,并且热通量将降至1 kW / m(2)以下,从而防止了随后的火灾蔓延。此外,火的能见度在150 s后恢复到25 m以上。这种新设计的喷淋系统可以通过简单的维护安装在一个侧壁上,而无需关闭隧道,而水也可以喷洒到另一壁上,以提供足够的壁冷却来保护隧道。它可以有效地应用于隧道的救援和保护。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号