首页> 外文期刊>铁道総研報告 >DEVELOPMENT OF PROTECTIVE RELAY FOR MIXED DIFFERENT FREQUENCY POWERS FOR AC ELECTRIC RAILWAYS
【24h】

DEVELOPMENT OF PROTECTIVE RELAY FOR MIXED DIFFERENT FREQUENCY POWERS FOR AC ELECTRIC RAILWAYS

机译:交流电铁道混合不同频率功率保护继电器的研制

获取原文
获取原文并翻译 | 示例

摘要

Hokuriku Shinkansen is electrified by a 30kV a.c.commercial frequency AT feeding system. As for the commercial frequency, Japan is divided into two zones, 60 Hz zone in the weatern part and 50Hz zone in the eastern part. Two different power frequencies exist in Hokuriku Shinkansen which passes the power frequency border between two different electric power supply companies. In case of a contact fault between two different power frequencies, a beat-formed large fault current will flow, which should be immediately detected and cut off.A protective relay for contact faults between the two different frequencies has been developed and has been put into practical use. The protective relay operates by detecting the 55Hz component specific to the current caused by the contact fault and also detecting power frequency of the opponent traction substation. They have been installed at a frequency-bordered sectioning post and at traction substations which sandwich the sectioning post.
机译:北陆新干线通过30kV交流商业频率AT馈电系统实现电气化。至于商业频率,日本分为两个区域,西部地区为60 Hz,东部地区为50Hz。北陆新干线有两个不同的电源频率,它们经过两个不同的供电公司之间的电源频率边界。如果两个不同的电源频率之间发生接触故障,则会流过拍频形式的大故障电流,应立即将其检测并切断。已开发出一种用于保护两个不同频率之间的接触故障的保护继电器实际使用。保护继电器通过检测由接触故障引起的电流所特有的55Hz分量并检测对方牵引变电站的工频来工作。它们已安装在有频率限制的分段杆和将分段杆夹在中间的牵引变电站中。