首页> 外文期刊>日本建築学会環境系論文集 >CFD・空調システムシミュレーション達成解析による室内混合損失の推定: CFDと達成した空調システムシミュレーションに関する研究 第2報
【24h】

CFD・空調システムシミュレーション達成解析による室内混合損失の推定: CFDと達成した空調システムシミュレーションに関する研究 第2報

机译:通过CFD /空调系统模拟成果分析估算室内混合损失:CFD研究和已实现的空调系统模拟第二次报告

获取原文
获取原文并翻译 | 示例
       

摘要

A coupled analysis of CFD and HVAC system simulations was carried out to assess the mixing energy loss in an air-conditioned office room where heating and cooling operate in the perimeter and interior zones simultaneously. To evaluate the mixing energy loss, we conducted two simulations; one was the case with the airflow mixing between the perimeter and interior zones and the other was the case without the airflow mixing. By comparing the required coil loads between the cases with and without the airflow mixing, the mixing energy loss was estimated. The accuracy of the coupled analysis was assessed by comparing the results with those from an experiment by Ito (1988).%本報(第2報)では、筆者らが開発してきたCFD+SS達成解析モデrnルを室内混合損失の予測に適用し、実験との比較からその予測精度rnおよび有効性を検証した。rn(1)室内温熱環境の評価においては、概ね実験と対応した結果が得rnられた。しかし、さらなる予測精度の向上のため、CFDの乱流モデrnルの改善や空調機器の同定の精度向上などの検討が今後必要である。
机译:对CFD和HVAC系统模拟进行了耦合分析,以评估空调办公室房间中混合能量的损失,在该办公室中,供暖和制冷同时在外围和内部区域运行。为评估混合能量的损失,我们进行了两个模拟;一种是在周边和内部区域之间进行气流混合的情况,另一种是没有进行气流混合的情况。通过比较在进行和不进行气流混合的情况下所需的盘管载荷,可以估算出混合能量损失。在本报告(第二份报告)中,作者开发的CFD + SS成就分析模型用于通过将结果与Ito(1988)的实验结果进行比较来评估耦合分析的室内混合损失。通过与实验对比,验证了其预测精度和有效性。 rn(1)在室内热环境的评估中,获得了与实验相对应的结果。但是,为了进一步提高预测精度,有必要研究CFD湍流模型的改进和空调设备识别的准确性。